Electrotechnology

The working words of power systems, protection, earthing and the grid control room.

283 terms38 shop talk10 topics

Electrotechnology is the shared vocabulary of everyone who generates, moves, protects and measures electricity, from the engineer running a fault study to the operator on the night desk of a grid control room. Much of it is defined with real precision, because a word like creepage distance or overvoltage category ends up as a number on a drawing and a dimension on a product. The same people also talk in a fast, clipped jargon on the radio and in the substation yard, and both registers sit side by side here.

The formal core covers power flow and power quality (active power, reactive power, power factor, harmonics, sag and swell), protection (fault current, IDMT curves, distance protection, differential protection, selectivity), earthing (the TN, TT and IT systems, equipotential bonding, touch voltage) and insulation coordination (BIL, clearance, CTI, partial discharge). EMC and measurement terms such as common-mode noise, true RMS and the insulation resistance test complete the toolkit.

Control-room and substation talk is where outsiders get lost. A breaker kicks, a relay flags, the 86 is latched, a feeder blinks, a squirrel takes out a transformer. Crews rack out a breaker, tag out the isolation points, prove dead, hang portable earths and work under a permit to work. They megger a cable, hipot a joint, ductor a contact and bring the thumper out to find a cable fault. Plenty of everyday words carry narrow meanings: stiff, dead, hot, trip, reach, burden and slip.

What marks an insider is precision about safety words and units. Nobody experienced calls a circuit dead until it has been proven dead, nobody mixes up kW, kVA and kvar, and anyone who swaps a disconnector for a circuit breaker in a switching order gets stopped. Regional habits matter too: British speakers say earth, isolator and discrimination where North Americans say ground, disconnect and coordination.

Who talks like this

Power system engineers, protection and control engineers, substation operators, grid dispatchers, high-voltage electricians, line crews, test technicians, EMC engineers and electrical designers.

Overheard on the job

Real-sounding lines from the floor, with every insider word decoded. Tap a highlighted word.

Line 4 tripped on zone 1, reclose failed so it's locked out, and the 86 on the flagged as well.

Plain EnglishThe line's distance protection saw a fault in its first, undelayed zone; the automatic reclose did not hold, so the breaker stays open, and the transformer's lockout relay also operated and is showing its indicator.

Rack it out, tag it out, prove it dead and get the on before I write the .

Plain EnglishWithdraw the breaker to its isolated position, hang danger tags on the isolation points, test for absence of voltage, and apply portable earthing leads before the permit to work is issued.

That is soft, every time the crusher starts we to 0.85 pu and the drives kick.

Plain EnglishThe supply has high source impedance, so starting the crusher motor drops the voltage to 85 percent of nominal and the variable-speed drives trip on undervoltage.

's fine but the Doble numbers on that bushing have doubled, I'd pull it before it lets go.

Plain EnglishThe insulation resistance test passed, but the insulation power factor test shows the bushing's losses have risen sharply, so it should be replaced before it fails.

is over 8 percent with all the drives on, and the fifth is going to ring with those caps.

Plain EnglishTotal harmonic distortion of the voltage is above 8 percent with every drive running, and the fifth harmonic is close to the resonant frequency of the capacitor bank.

We're not N-1 with Westside out, so hold that until after the evening peak.

Plain EnglishWith the Westside line out of service, losing one more element would overload the system, so planned switching should wait until demand falls.

on the bushing, the feeder twice and then locked out.

Plain EnglishAn animal bridged a transformer bushing to earth; the recloser tried twice, causing two momentary outages, then stayed open because the fault persisted.

The glossary

All 283 terms, grouped by topic.

283 shown

Power Systems & Grid

45 terms

How power flows, how its quality is described and how grid operators keep supply and demand in balance.

  • ACalso a-c, alternating current
    The standard abbreviation for alternating current.
  • Active poweralso real power, true power
    The part of electrical power that does real work, averaged over each cycle and measured in watts.
  • Anchor pylonalso tension tower, dead-end tower
    A heavy-duty transmission tower designed to handle high lateral mechanical tension.
  • Product of RMS voltage and RMS current, the figure transformers, generators and UPS units are rated on.
  • Black startalso blackstart
    Restarting a power system from total shutdown using generators that can start without any outside supply.
  • A device inserted into a circuit to increase or regulate the voltage.
  • Brownoutalso sustained undervoltage
    Sustained drop in supply voltage, caused by overload or applied on purpose to cut demand during a shortage. Shop talk
  • Busalso busbar, bus bar
    Rigid conductor or common node in a substation or switchboard where several circuits connect and share power.
  • A complete, closed path through which electric current can flow.
  • Delta connectionalso mesh connection
    A three-phase electrical configuration where components are connected end-to-end to form a closed loop.
  • Electric power transmissionalso transmission, bulk power transport
    The bulk transfer of electrical energy from generating power plants to electrical substations.
  • Harmonicsalso harmonic distortion
    Voltage or current components at whole multiples of the supply frequency, produced mostly by nonlinear loads.
  • Islandingalso loss of mains, LOM
    Condition where part of a network stays energised by local generation after being cut off from the main grid.
  • A single phase or branch of a polyphase electrical system. Shop talk
  • Line dropalso voltage drop
    The loss of voltage along a transmission or distribution line due to its natural impedance.
  • The ratio of average electrical load to peak load over a specific period.
  • Load sheddingalso load shed, rolling blackouts
    Deliberate disconnection of blocks of customer load to stop frequency or voltage from collapsing.
  • MSBalso main switchboard
    The primary electrical panel that distributes power from the source to downstream sub-boards.
  • N-1 criterionalso N minus one, single contingency criterion
    Planning rule that a grid must stay within limits after losing any single major element such as a line or generator.
  • A grid condition where the alternating current frequency rises above its nominal target value.
  • Per-unit systemalso per unit, pu
    Shorthand that states voltages, currents and impedances relative to chosen base values, so 1.0 means nominal.
  • The primary professional society for electrical engineers working in the power industry.
  • A technique or equipment used to improve the power factor of an electrical installation.
  • Phasealso line
    A single distinct oscillating voltage or current in a multi-conductor electrical system.
  • Polyphasealso multi-phase
    Describing an electrical system that uses multiple alternating currents with staggered phase angles.
  • An electrical network that carries multiple alternating currents with staggered phase angles.
  • Ratio of active power to apparent power, showing how much of the current drawn does useful work.
  • Power failurealso power outage, blackout
    An unplanned interruption of the electrical supply to a load or facility.
  • Pylonalso transmission tower
    A tall steel lattice structure that supports overhead high-voltage transmission lines.
  • Quarter-phasealso two-phase
    An older AC power system utilizing two alternating currents separated by 90 electrical degrees.
  • Reactive poweralso vars, Q
    Power that surges back and forth between the source and the fields of inductors and capacitors, doing no net work.
  • An inductive component used to limit fault currents or control voltage on a power system.
  • The current that flows back to the power source to complete an electrical circuit.
  • Sagalso voltage sag, voltage dip
    Brief drop in RMS supply voltage, usually to between 10 and 90 percent of nominal, lasting up to about a minute.
  • Split-phase poweralso single-phase three-wire system, Edison system
    A single-phase distribution system that provides two separate voltages using a center-tapped transformer.
  • Stiffalso strong
    Describes a supply with low source impedance, so its voltage barely moves when load or fault current changes. Shop talk
  • Swellalso voltage swell
    Short-lived rise in RMS voltage above normal, often seen on the healthy phases during an earth fault.
  • SWERalso single-wire earth-return
    A single-wire earth-return system used to supply single-phase power to remote areas.
  • Tappingalso tap
    A connection point made along a transformer winding to allow for voltage adjustment.
  • THDalso total harmonic distortion
    Total harmonic distortion: the combined size of all harmonics relative to the fundamental, as a percentage.
  • To change the voltage and current levels of alternating current power using magnetic induction.
  • Transformeralso tranny, tx
    A static electromagnetic device that transfers electrical energy between circuits at changed voltage levels.
  • UHValso ultra-high voltage
    Ultra-high voltage, referring to transmission systems operating above 800 kilovolts.
  • A backup power system that provides instantaneous emergency electricity to critical loads when the main supply fails.
  • UPSalso uninterruptible power supply
    Uninterruptible power supply, a battery or flywheel system that instantly provides backup power during an outage.

Protection & Faults

39 terms

Fault currents, the relays and breakers that clear them, and the settings that decide which device trips first.

  • 86 relayalso 86, lockout relay
    Lockout relay that latches after a serious trip and holds breakers open until someone resets it by hand. Shop talk
  • ACRalso recloser
    An automatic circuit recloser used on distribution networks.
  • The explosive pressure wave caused by a high-energy electrical arc.
  • Arc faultalso arcing fault
    An unintended electrical discharge through the air between conductors.
  • Explosive release of heat, light and pressure when an electric arc forms through air between energised parts.
  • Auto-reclosealso autoreclose, reclosing
    Automatic closing of a breaker shortly after a fault trip, restoring supply when the fault was only transient.
  • Blinkalso momentary, momentary interruption
    Momentary outage customers see when an upstream breaker or recloser trips and recloses on a passing fault. Shop talk
  • To draw enough overcurrent to melt the sacrificial element in a fuse and break the circuit. Shop talk
  • Breaking capacityalso interrupting rating, interrupting capacity
    Highest fault current a circuit breaker or fuse can interrupt safely at its rated voltage.
  • Cut-outalso fused cutout, drop-out fuse
    A fused assembly connecting a customer service drop to the overhead distribution lines.
  • Scheme that compares current entering and leaving a protected zone and trips when the two disagree.
  • Distance protectionalso impedance protection, 21
    Line protection that measures impedance to a fault and trips fastest for faults close to the relay.
  • Earth faultalso ground fault, line-to-ground fault
    Fault in which a live conductor makes unintended contact with earth or with earthed metalwork.
  • EFalso earth fault
    An abbreviation for earth fault, a condition where current escapes the intended circuit and flows to ground.
  • Any abnormal condition that causes current to bypass its intended path.
  • Fault currentalso short-circuit current, fault level
    Abnormally high current that flows when insulation fails and a short circuit or earth fault forms.
  • A sacrificial protection device containing a conductive element that melts to safely break a circuit during an overcurrent event.
  • A bare, easily melted metallic strand used as the replaceable sacrificial element in older rewirable protective devices.
  • IDMTalso inverse time overcurrent, 51
    Inverse definite minimum time: an overcurrent curve that trips faster as current rises, down to a set minimum.
  • IEDalso Intelligent Electronic Device
    A microprocessor-based controller used in substations to monitor, protect and control power equipment.
  • Interrupting timealso clearing time
    The total duration from the moment a trip coil is energized until the fault current is completely extinguished.
  • Let-throughalso let-through current, let-through energy
    The amount of fault current or surge energy that passes through a protective device before it operates.
  • Lost neutralalso broken neutral, open neutral
    A dangerous fault condition where the neutral return path to the supply transformer is broken.
  • Nuisance tripalso false trip, spurious trip
    Protective device opening with no real fault present, usually from bad settings, leakage or transients. Shop talk
  • An abbreviation for overcurrent protective device, a component that breaks a circuit during excessive current flow.
  • A component designed to interrupt an electrical circuit when the current exceeds a predetermined safe limit.
  • The unwanted operation of a protection relay or circuit breaker for a fault located outside its intended zone.
  • Pickupalso pick-up, operate value
    Threshold at which a protection element starts to operate, and the moment the measured value crosses it.
  • Protection relayalso protective relay, relay
    Device that watches currents and voltages and orders a circuit breaker to trip when it detects a fault.
  • Reachalso zone reach
    Extent of line or network a distance relay zone is set to cover, expressed as an impedance.
  • A safety switch that trips a circuit when it detects leakage current to earth.
  • Selectivityalso discrimination, coordination
    Arranging protection so only the device nearest a fault operates and the rest of the system stays in service.
  • Short circuitalso short
    Unintended low-impedance path between conductors at different potentials, bypassing the load.
  • A destructive fault condition where a three-phase motor loses one of its supply phases.
  • SPDalso surge protective device, surge protector
    A surge protective device used to limit transient overvoltages and divert surge currents.
  • A control relay designed to actuate its contacts after a specific duration.
  • Tripalso trip out, trip-out
    To open a circuit breaker automatically through its protection, or to order a breaker open by command.
  • Trip-switchalso trip
    A protective electrical switch that automatically opens a circuit when it detects a fault. Shop talk
  • X/R ratioalso X over R
    Ratio of reactance to resistance in the fault path, which sets how large and slow the DC offset in fault current is.

Earthing & Safety

26 terms

Earthing systems, bonding, shock voltages and the words that separate a safe isolation from a dangerous one.

  • An electrical fault where a live conductor touches the metallic casing of equipment.
  • Deadalso de-energised, de-energized
    Isolated from every source, proven free of voltage and safe to work on. Shop talk
  • Earth fault loop impedancealso Zs, loop impedance
    Total impedance of the path a fault current takes from the source, through an earth fault and back again.
  • Earthingalso grounding
    The practice of connecting electrical equipment and systems to the general mass of the earth.
  • Earthing systemalso earthing arrangement, system earthing
    Arrangement describing how a supply's neutral and an installation's exposed metalwork are connected to earth.
  • Equipotential bondingalso bonding, protective equipotential bonding
    Connecting metal parts together so they sit at one potential and no dangerous voltage appears between them.
  • Groundalso earth, Grounded
    A direct, low-impedance electrical connection to the earth, establishing a zero-voltage reference point for a system.
  • Ground wirealso earth wire, earth conductor
    A dedicated conductor that connects electrical equipment enclosures or system neutrals to the earth electrode.
  • Hotalso live, energized
    Shop word for live or energised, and in North America the everyday name for a phase conductor. Shop talk
  • IT systemalso isolated system, unearthed system
    Earthing arrangement in which the source is isolated from earth or earthed only through a high impedance.
  • The small amount of current that escapes through insulation to ground under normal operating conditions.
  • Livealso energised, energized
    Connected to a source of voltage, or describing a conductor meant to be energised in normal use.
  • Live conductoralso active conductor
    Any conductor that is energized and intended to carry current during normal operation.
  • Live wirealso hot wire
    An informal term for an energized, ungrounded phase conductor. Shop talk
  • PEalso protective earth, protective earthing
    The designated conductor used to connect exposed metallic parts of equipment to the main earthing terminal.
  • PEN conductoralso combined neutral and earth, CNE conductor
    Single conductor that serves as both the neutral and the protective earth in a TN-C network.
  • Permit to workalso PTW, permit
    Formal written authority to work on equipment that has been isolated, earthed and declared safe.
  • Portable earthsalso grounds, protective grounds
    Removable earthing leads clamped onto isolated conductors to short them together and to earth during work. Shop talk
  • Prove deadalso test before touch, live-dead-live
    To test isolated equipment with a verified voltage detector and confirm no voltage before anyone touches it. Shop talk
  • RCDalso RCCB, GFCI
    Residual current device: trips when the current going out on the live conductors does not all come back.
  • Step voltagealso step potential
    Voltage between a person's feet across the ground surface near an earth fault or an earthed structure.
  • TN-C-S systemalso PME, protective multiple earthing
    Supply earthing in which a combined neutral and earth conductor splits into separate ones at the installation.
  • Earthing arrangement where the source is earthed and installation metalwork connects back to it by a protective conductor.
  • Touch voltagealso touch potential, prospective touch voltage
    Voltage a person bridges between a hand on faulted metalwork and their feet or other hand during a fault.
  • TT systemalso TT earthing
    Earthing arrangement where the supply and the installation each have their own separate earth electrode.
  • Ungroundalso Ungrounded, floating
    To deliberately remove the electrical connection between a circuit and the earth.

Insulation & Coordination

17 terms

Clearances, creepage, impulse levels and the ways insulation degrades and fails.

  • Arcoveralso flashover, tracking
    An electrical discharge that bridges the surface of an insulator.
  • BILalso basic insulation level, LIWL
    Basic lightning impulse insulation level: the peak impulse voltage equipment must withstand without breakdown.
  • Clearancealso air clearance, electrical clearance
    Straight-line air gap between two conductive parts, the dimension that decides whether a surge can flash across.
  • Coronaalso corona discharge
    Faint glowing discharge around high-voltage conductors where the air is overstressed, causing noise and loss.
  • Corona dischargealso corona
    A luminous electrical discharge caused by the ionization of fluid surrounding a high-voltage conductor.
  • Creepage distancealso creepage, creep distance
    Shortest route over an insulating surface from one conductive part to another, the dimension that resists tracking.
  • CTIalso comparative tracking index
    Comparative tracking index: voltage an insulating material withstands before tracking under a wet contamination test.
  • Flashoveralso flash-over
    Disruptive discharge over or around insulation that creates a short circuit through the air.
  • The specific potential difference at which an electrical discharge bridges the gap across or along an insulator.
  • A material with high electrical resistance used to isolate conductors and prevent current leakage.
  • Insulation coordinationalso insulation co-ordination
    Sizing insulation and surge arresters together so any flashover lands at a cheap, self-restoring point, not inside plant.
  • Lichtenberg figurealso electrical treeing
    A branching, tree-like pattern created by high-voltage electrical discharges along or inside an insulating material.
  • Overvoltage categoryalso OVC, installation category
    Class from I to IV ranking equipment by its position in an installation and the surges it must survive.
  • Partial dischargealso PD, discharge activity
    Tiny discharge in a void, on a surface or at a sharp edge that never spans the whole insulation, an early sign of decay.
  • Grade from 1 to 4 describing how much conductive dirt and moisture can settle on insulation in a location.
  • Surge arresteralso lightning arrester, arrestor
    Device that clamps transient overvoltages by diverting surge current to earth, then returns to insulating.
  • Trackingalso surface tracking, carbon tracking
    Conductive carbon trail that leakage arcs through dirt and moisture gradually burn across an insulating surface.

Machines & Switchgear

48 terms

Transformers, motors, switchgear and the instrument transformers that feed protection and metering.

  • The physical mechanism that drives the contacts of a switch or breaker.
  • Alternatoralso synchronous generator
    A generator that converts mechanical energy into alternating current.
  • A transformer that uses a single continuous winding for both primary and secondary circuits.
  • Buchholz relayalso gas relay, 63
    Gas and oil-surge relay in the pipe between a transformer tank and its conservator that detects internal faults.
  • Burdenalso VA burden, secondary load
    Load connected to the secondary of an instrument transformer, stated in VA or ohms.
  • Circuit breakeralso CB, breaker
    A mechanical switching device capable of making, carrying and breaking currents under normal and fault conditions.
  • To reverse the direction of electric current in a specific winding or circuit branch.
  • The process of transferring current from one conducting path to another.
  • An electrically controlled switch used for switching an electrical power circuit.
  • A device or assembly that governs the performance of an electric motor or system.
  • Core lossalso iron loss, no-load loss
    The electrical energy dissipated as heat within the magnetic core of an AC device.
  • CTalso current transformer
    Current transformer: an instrument transformer that scales large primary currents down to a standard secondary.
  • A solid-state device that directly converts alternating current at one frequency to a lower frequency.
  • Disconnectoralso isolator, disconnect switch
    Off-load switch that provides a visible isolating gap but is not built to make or break load current.
  • Dynamoalso DC generator
    An electrical generator that produces direct current using a commutator.
  • Electrical busalso busbar, bus
    A heavy conductor used as a common connection point for multiple circuits.
  • Field coilalso excitation coil, field winding
    An electromagnet winding used to generate a steady magnetic field in a rotating machine.
  • The permanent magnet or electromagnet that provides the magnetic field in a motor or generator.
  • Hammer breakalso trembler, vibrator
    An electromechanical interrupter mechanism that uses a vibrating armature to rapidly make and break a circuit.
  • A resistive component that converts electrical energy directly into thermal energy.
  • Induction motoralso asynchronous motor
    An alternating current motor where the rotor current is induced by the magnetic field of the stator.
  • Inrush currentalso inrush, switch-on surge
    Large transient current drawn when a transformer, motor or capacitive load is first switched on.
  • Interpolealso commutating pole
    A small auxiliary magnetic pole placed between the main poles of a direct current machine to improve commutation.
  • IPMalso interior permanent magnet
    An interior permanent magnet motor has its magnetic materials embedded inside the rotor structure.
  • Mercury arc rectifieralso mercury vapor rectifier
    A historic glass or steel vacuum tube device used to convert high-voltage alternating current into direct current.
  • NOalso normally open
    A contact state where the circuit remains open when the device is in its resting state.
  • The operating state of an electrical machine when it is energized but not doing any external work.
  • OLTCalso on-load tap changer, load tap changer
    On-load tap changer: a transformer switch that changes the turns ratio under load to regulate voltage.
  • Paraformeralso parametric transformer
    A specialized type of transformer that transfers energy through variations in magnetic reluctance rather than mutual inductance.
  • A historic type of rotary converter used to change alternating current to direct current using rotating brushes.
  • An early type of synchronous motor driven by magnetic pulses from a tuning fork.
  • Potheadalso cable termination
    Field name for the termination where an underground power cable meets an overhead line or equipment. Shop talk
  • Primaryalso primary winding
    The input winding of a transformer or the main current-carrying circuit in an instrument transformer.
  • An early electromechanical machine used to convert alternating current to direct current.
  • A magnetic pole that physically sticks out from the rotor core of an electric machine.
  • Describes a motor or generator where the field coils are wired in series with the armature.
  • SF6also sulphur hexafluoride, sulfur hexafluoride
    Sulphur hexafluoride: a dense, highly insulating gas used to quench arcs in high-voltage switchgear.
  • Slipalso rotor slip
    Shortfall between the speed of an induction motor's rotating field and the actual speed of its rotor.
  • A channel cut into the magnetic core of a stator or rotor to hold electrical windings.
  • SPMalso surface permanent magnet
    A surface permanent magnet motor, where magnets are mounted on the exterior of the rotor.
  • Squirrel-cage motoralso squirrel-cage induction motor
    An AC induction motor featuring a rotor made of parallel conductive bars shorted by end rings.
  • Switchgearalso SWGR, gear
    Assemblies of breakers, switches, fuses, busbars and enclosures that control and protect power circuits.
  • Synchroalso autosyn, selsyn
    A specialized rotary transformer that measures and transmits the angular position of a rotating shaft.
  • The speed at which the magnetic field rotates in an AC induction motor.
  • The effective mechanical output rating of a motor based on its heat dissipation limits.
  • Vector groupalso vector group designation, connection symbol
    Code stating how a three-phase transformer's windings are connected and the phase shift between them.
  • VTalso voltage transformer, PT
    Voltage transformer: an instrument transformer that steps high voltage down to a standard level for relays and meters.
  • Wildalso wild AC, wild frequency
    Describes AC power with an unregulated, fluctuating frequency. Shop talk

EMC & Electronics

11 terms

Interference, coupling and the circuit fundamentals behind electromagnetic compatibility.

  • Common-modealso CM, longitudinal
    Describes signals or noise present equally, in the same phase, on both conductors of a pair relative to ground.
  • Compatibilityalso electromagnetic compatibility
    The ability of different electrical devices or systems to operate in the same environment without causing mutual interference.
  • Conducted interferencealso conducted emissions, conducted noise
    Electrical noise or unwanted signals that travel along physical wires and cables.
  • Crosstalkalso XT, cross-talk
    Unwanted coupling of a signal from one conductor or channel into a neighbouring one.
  • EMCalso electromagnetic compatibility
    Electromagnetic compatibility: a product neither upsets nearby equipment with its noise nor gets upset by theirs.
  • EMIalso electromagnetic interference
    Electromagnetic interference: unwanted electrical noise that disturbs the operation of a circuit or system.
  • ESDalso electrostatic discharge, static zap
    Electrostatic discharge: sudden flow of built-up static charge that can destroy or upset electronics.
  • Ground loopalso earth loop
    Unintended current path formed when connected equipment is earthed at points of different potential.
  • Immunisationalso immunization
    The process of protecting signalling and control circuits from electromagnetic interference caused by nearby power lines.
  • Impedancealso Z
    Total opposition a circuit offers to alternating current, combining resistance and reactance, in ohms.
  • Tendency of alternating current to crowd toward the surface of a conductor as frequency rises.

Measurement & Testing

21 terms

Units, meters and field tests used to prove equipment healthy before and after it goes into service.

  • Clamp meteralso clamp-on ammeter, amp clamp
    Handheld meter whose jaws close around a conductor to measure current without breaking the circuit.
  • Digital meteralso smart meter, DMM
    An electronic device used to measure and display electrical quantities using a digital readout.
  • Doble testalso power factor test, tan delta test
    Insulation power factor test on transformers, bushings and breakers, named after a well-known test set maker. Shop talk
  • Ductoralso micro-ohmmeter, DLRO
    Shop name for a micro-ohmmeter used to measure very low contact and joint resistances. Shop talk
  • A field strength meter is a portable instrument used to measure the electric or magnetic field intensity in a given area.
  • Hipotalso hi-pot, high-potential test
    High-potential test: applying a voltage well above working level to prove insulation will not break down. Shop talk
  • Insulation resistance testalso IR test, megger test
    DC test that applies a high voltage between conductors and earth and reads leakage resistance in megohms.
  • Interaxisalso interaxis error
    A measurement of the perpendicularity error between different sets of resolver windings.
  • A self-contained unit that applies a controllable electrical load to a power source.
  • Meggeralso megohmmeter, IR tester
    To test insulation resistance with a high-voltage DC tester; also the jobsite name for the tester itself. Shop talk
  • Milliohmmeteralso microohmmeter
    A specialized test instrument designed to measure very low electrical resistance.
  • PATalso portable appliance testing
    The routine inspection and electrical testing of movable appliances to ensure they are safe to use.
  • The total amount of electrical energy drawn by a load over a specific period.
  • Pressure wirealso pilot wire, sense wire
    A dedicated sensing conductor used to measure the voltage at a remote point in an electrical network.
  • RMSalso root mean square, effective value
    Root mean square: the effective value of an alternating quantity, giving the same heating as that DC value.
  • Thumperalso surge generator, cable thumper
    Field nickname for a surge generator that pulses a faulted cable so the fault can be heard and pinpointed. Shop talk
  • The process of synchronizing clocks and frequency standards across multiple remote sites.
  • Time-of-use meteralso TOU meter
    An electricity meter that records power consumption in different tariff periods based on the time of day.
  • True RMSalso TRMS
    Describes a meter or reading that computes the real RMS of any waveform, not one scaled from a sine-wave average.
  • VACalso volts AC
    Volts alternating current, the unit used to specify the potential difference in an AC circuit.
  • varalso VAr, volt-ampere reactive
    Unit of reactive power, the volt-ampere reactive, written lower case and usually scaled to kvar or Mvar.

Control Room & Substation Talk

20 terms

Radio calls, switching language and yard slang from grid control rooms and substations.

  • Backfeedalso back-feed, reverse feed
    Power arriving at a circuit from an unexpected direction, such as a generator or second supply feeding back. Shop talk
  • Bumpalso bump test, jog
    To energise a motor for a split second to check its direction of rotation before running it properly. Shop talk
  • Chatteralso contact chatter, relay chatter
    Rapid repeated opening and closing of relay or contactor contacts, usually from marginal voltage or vibration. Shop talk
  • The state of a switch or circuit breaker where its contacts are physically touching to allow current flow.
  • DC groundalso battery earth fault, DC earth fault
    Unwanted earth fault on a substation battery or DC control supply, which normally floats free of earth. Shop talk
  • Dead busalso dead bar, dead busbar
    Busbar with no voltage on it, the condition that lets a breaker close without synchronising checks. Shop talk
  • An industrial digital network protocol used for real-time distributed control of automated equipment.
  • Flagalso target
    Indicator on a protection relay showing which element or phase operated; also the verb for it showing. Shop talk
  • Gallopingalso conductor galloping, dancing
    Large, slow vertical swinging of overhead line conductors driven by wind on ice-coated wires.
  • Hot stickalso hotstick, operating pole
    Insulated fibreglass pole used to operate, test or earth high-voltage equipment from a safe distance. Shop talk
  • Kickalso kick out, pop
    Shop verb for a breaker, overload or relay tripping, as in the breaker kicked. Shop talk
  • Magic smokealso let the smoke out
    Joking name for the smoke a burnt-out component releases, as if the smoke were what made it work. Shop talk
  • OPCalso Open Platform Communications, OLE for Process Control
    A standard software interface that allows industrial control hardware to share data with Windows-based applications. Shop talk
  • Rack outalso rack-out, withdraw
    To wind a withdrawable breaker out of its connected position in metal-clad switchgear to isolate it. Shop talk
  • Ring outalso buzz out, bell out
    To check continuity and identity of every core of a cable end to end before termination or after a fault. Shop talk
  • SCADAalso supervisory, telecontrol
    Supervisory control and data acquisition: the system that lets a control room watch and switch remote plant.
  • Squirrelalso animal contact, squirrel outage
    Control-room shorthand for an animal-caused fault, typically a squirrel or bird bridging live parts. Shop talk
  • Switching orderalso switching programme, switching program
    Written step-by-step sequence of operations used to isolate or restore equipment safely.
  • Tag outalso LOTO, lock out tag out
    To hang a danger tag on an isolation point so nobody operates it while people work downstream. Shop talk
  • Time switchalso timer switch
    A mechanical or electronic switch that automatically controls a circuit based on a clock.

Physics & Electromagnetism

41 terms

The core principles of magnetic fields, induction and the physical laws that make electrical generation work.

  • A theoretical time coordinate used in electromagnetic field calculations to describe field states in the future.
  • The strong mechanical force exerted on a current-carrying conductor in a magnetic field.
  • The phenomenon where two or more overlapping waves combine to produce a wave of greater amplitude.
  • Coulomb forcealso electrostatic force
    The fundamental electrostatic force of attraction or repulsion between electrically charged particles.
  • The proportionality factor in the equation linking electrostatic force, charge, and distance.
  • The physical principle describing how the electrostatic force between charges decreases with distance.
  • Currentalso electric current
    The rate of flow of electric charge through a conductor.
  • Displacementalso electric displacement
    The shift of bound charges within a dielectric material when subjected to an external electric field.
  • A quantity representing the rate of change of the electric displacement field over time.
  • Electric currentalso current
    The directed flow of electric charge through a conductive medium.
  • Electric fieldalso E-field
    A region of space where an electric charge experiences a force.
  • The total measure of an electric field passing perpendicularly through a specific surface area.
  • Electric potentialalso voltage potential
    The amount of work energy needed to move a unit of electric charge from a reference point to a specific location.
  • Relating to stationary electric charges or fields rather than continuous electric currents.
  • Electrostatic forcealso Coulomb force
    The physical attraction or repulsion between particles due to their electric charge.
  • H-fieldalso magnetic field intensity, magnetic field strength
    The magnetic field intensity generated by free electrical currents, independent of the magnetic properties of the surrounding medium.
  • The duration of a single alternating current power cycle. Shop talk
  • The condition where the alternating current waveform arrives ahead of the voltage waveform.
  • An early type of capacitor made from a glass jar with inner and outer metal foil coatings.
  • The combined electric and magnetic force exerted on a charged particle moving through an electromagnetic field.
  • Lorenz gaugealso Lorenz gauge condition
    A mathematical condition applied to electromagnetic potentials to simplify Maxwell's equations.
  • The closed path followed by magnetic flux lines in an electrical machine or device.
  • Magnetic equatoralso aclinic line
    The imaginary line around the Earth where the geomagnetic field is perfectly horizontal.
  • Magnetic momentalso magnetic dipole moment
    A vector quantity dictating how a magnetic object aligns with an external magnetic field.
  • A closed loop in an electrical circuit that contains no other loops inside it.
  • A mathematical method used to calculate unknown currents in a planar circuit.
  • A theoretical current assumed to flow continuously around a single mesh in a circuit.
  • The end of a magnet where magnetic field lines emerge.
  • Ohmic resistancealso DC resistance
    The pure direct-current resistance of a conductor or component.
  • An older term for the ability of a dielectric material to store electrical energy in an electric field.
  • An idealized model of an electrically charged object with no physical dimensions.
  • A simplified physical model of an object treated as having mass but zero volume.
  • The direction of an electric field or the designation of positive and negative terminals.
  • The distortion of alternating current flow in a conductor caused by the magnetic fields of nearby parallel conductors.
  • Pertaining to the portion of an AC circuit that stores and releases energy through magnetic or electric fields.
  • The intrinsic property of a material that quantifies how strongly it opposes the flow of electric current.
  • The exact past time when an electromagnetic wave was emitted to reach an observer at the present moment.
  • The region of a magnet where magnetic flux lines enter the material.
  • Space permeabilityalso permeability of free space, magnetic constant
    The physical constant that defines how easily a magnetic field can form in a classical vacuum.
  • The intrinsic magnetic field generated by an elementary particle due to its quantum spin.
  • Voltagealso potential difference, electromotive force
    The difference in electrical potential between two points that drives current through a circuit.

Cables & Conductors

15 terms

Wire types, insulation ratings, pulling tensions and the terminology used for overhead lines and underground cables.

  • A multi-core power cable where the insulated conductors are wrapped together by a common insulating belt.
  • Cable corealso core
    The central current-carrying conductor and its immediate insulation within a larger cable.
  • Cable jointalso splice
    An engineered splice connecting two lengths of power cable.
  • A physical material or wire designed to carry electric current with minimal resistance.
  • Connect upalso wire up, hook up
    To physically join cables, wires, or equipment to establish an electrical circuit. Shop talk
  • A technique of transposing the metallic sheaths of single-core power cables to cancel out induced currents.
  • Electric mainalso mains cable, incoming main
    The primary supply cable bringing power from the utility network into a building.
  • Line conductoralso phase conductor, line wire
    A wire or cable that carries normal operating current from a power source to a load.
  • McIntire jointalso twisted sleeve joint, McIntire splice
    A historic method of splicing overhead line wires using a twisted double-tube sleeve. Shop talk
  • Neutral conductoralso neutral
    The wire in an alternating current system that provides the return path for load current.
  • A robust, insulated assembly of conductors used to transmit bulk electrical energy.
  • A flexible cable assembly used to connect appliances and portable equipment to the mains supply.
  • A flexible cable used to supply mains electricity to a device or test equipment. Shop talk
  • To replace the existing wires on a transmission or distribution line with new ones.
  • A single wire that is twisted together with others to form a flexible cable or conductor.

Questions people ask

What is the difference between creepage distance and clearance?

Clearance is the gap a spark would jump straight through the air between two conductive parts, and it guards against flashover from voltage peaks and surges. Creepage distance is the route leakage current would crawl over the insulating surface between the same parts, and it guards against tracking caused by dirt and moisture over time. Clearance depends mainly on impulse voltage and overvoltage category, creepage on working voltage, pollution degree and the material's CTI. Creepage can never be less than clearance.

What do TN, TT and IT earthing systems mean?

The first letter describes the source: T means its neutral is directly earthed, I means it is isolated or earthed through a high impedance. The second letter describes the installation's metalwork: T means it has its own earth electrode, N means it connects back to the source neutral through a protective conductor. TN gives fault currents high enough to trip breakers, TT relies on RCDs because fault current passes through soil, and IT keeps running after a first earth fault.

What is the difference between kW, kVA and kvar?

Kilowatts measure active power, the part that does useful work and drives the energy bill. Kilovars measure reactive power, the power that surges in and out of magnetic and electric fields each cycle without doing net work. Kilovolt-amperes measure apparent power, the combination of the two, which is what heats cables and transformers. The ratio of kW to kVA is the power factor, so a 1000 kVA transformer at 0.8 power factor delivers only 800 kW.

What is the difference between a disconnector and a circuit breaker?

A circuit breaker is built to make and break load current and to interrupt fault currents of tens of kiloamperes automatically when its protection tells it to. A disconnector, also called an isolator, only provides a safe isolating gap and is opened after the breaker has already interrupted the current. Opening a disconnector on load draws a dangerous arc, so interlocks and switching orders always put the breaker first and the disconnector second.

What is the difference between a megger test and a hipot test?

A megger test, properly an insulation resistance test, applies a DC voltage of typically 500 V to 5 kV and reports a resistance in megohms or gigohms, which is trended over time to reveal moisture and contamination. A hipot applies a higher voltage, well above the working level, for a fixed time and gives a pass or fail: the insulation either withstands it or breaks down. Crews usually megger first, then hipot.

Every entry is checked by people who use the words.

Terms are validated with working professionals and approved by our editorial committee before they are published. See how a word earns its place.