Earth fault loop impedance

nounStandard termElectrotechnology

Total impedance of the path a fault current takes from the source, through an earth fault and back again.

Earth fault loop impedance, Zs, is the sum of the source transformer winding, the line conductor out to the fault and the protective return path back to the source. Nominal voltage divided by Zs gives the prospective earth fault current, which must be high enough to operate the protective device within the required disconnection time. Electricians measure it with a loop tester at the far end of each circuit and compare it with the maximum tabulated for that breaker or fuse.

Heard on the job

Zs at the far socket is 1.9 ohms and the max for a B32 is 1.37, so the earth fault loop impedance fails, it needs bigger cable or an RCD.

Insider tip

Ze is the external part measured at the origin with the main earth disconnected; Zs is Ze plus the circuit's own conductors.

Also heard as

  • Zs
  • loop impedance