Doble test

nounShop talkElectrotechnology

Insulation power factor test on transformers, bushings and breakers, named after a well-known test set maker.

A Doble test measures the power factor or dissipation factor of insulation by applying an AC voltage, commonly 10 kV, and comparing the in-phase loss current with the capacitive charging current. A rising percentage on a bushing or winding compared with nameplate or earlier results points to moisture, contamination or ageing. The brand name stands for the whole family of tests, including capacitance, excitation current and tip-up checks.

Heard on the job

Doble test on the C phase bushing came back at 0.9 percent against 0.3 on the nameplate, that bushing is coming out.

Also heard as

  • power factor test
  • tan delta test
  • dissipation factor test

Do not mix it up with

  • Power factor: Insulation power factor describes losses in a dielectric, not the power factor of a load.