TN-C-S system

nounStandard termElectrotechnology

Supply earthing in which a combined neutral and earth conductor splits into separate ones at the installation.

A TN-C-S system uses a combined protective and neutral (PEN) conductor in the distribution network, earthed at many points, and splits it into separate neutral and protective earth conductors at the service position. It is the most widespread arrangement for new urban supplies in the UK, Australia and North America. Its weak point is a broken PEN: if the combined conductor opens, installation metalwork can rise toward line voltage, so rules restrict its use for EV chargers, caravans and outdoor metal.

Heard on the job

It's a TN-C-S supply, so the EV charger needs open-PEN protection or its own earth rod before we connect it.

Insider tip

UK electricians call it PME, Australians MEN (multiple earthed neutral); the arrangement is the same.

Also heard as

  • PME
  • protective multiple earthing
  • MEN