DC ground

nounShop talkElectrotechnology

Unwanted earth fault on a substation battery or DC control supply, which normally floats free of earth.

A DC ground is an insulation fault from either pole of the substation DC system, usually 110 V or 125 V, to earth. The system is designed to run unearthed, so one ground causes no trip but is alarmed by a detector, while a second ground on the opposite pole can operate breakers falsely or stop them tripping. Finding one means briefly removing circuits one at a time while watching the detector, a slow and nervous job.

Heard on the job

Positive DC ground alarm at Northgate, 40 kilohms and dropping, start splitting circuits but don't touch the trip supplies without calling me.

Also heard as

  • battery earth fault
  • DC earth fault
  • DC earth