Burden

nounStandard termElectrotechnology

Load connected to the secondary of an instrument transformer, stated in VA or ohms.

Burden is the total impedance placed across a CT or VT secondary by relays, meters and connecting leads, stated in volt-amperes at rated secondary current or voltage. A CT rated 15 VA at 5 A can drive 0.6 ohm and still hold its accuracy class. Long lead runs, especially with 5 A secondaries, eat into the burden and can push a protection CT into saturation during a fault.

Heard on the job

Lead run from the yard CTs to the relay room is 300 m, that's most of the burden on a 5 A secondary, go 1 A next time.

Also heard as

  • VA burden
  • secondary load