Fault current

nounStandard termElectrotechnology

Abnormally high current that flows when insulation fails and a short circuit or earth fault forms.

Fault current is the current driven through a short circuit or earth fault, limited only by the impedance of the source, the network and the fault itself. It can be tens of times normal load current, from a few kiloamperes on a distribution feeder to over 60 kA on a large station busbar. Its value sets breaker breaking capacity, busbar and cable withstand ratings, relay settings and arc flash energy.

Heard on the job

Max fault current at the LV board is 48 kA, so those 36 kA breakers in the old panel are underrated and have to go.

Insider tip

Fault level is often quoted in MVA (1.732 x voltage x fault current), so 'the 11 kV bus is 250 MVA' is a statement about fault current, not load.

Also heard as

  • short-circuit current
  • fault level
  • available fault current