Nuisance trip

nounShop talkElectrotechnology

Protective device opening with no real fault present, usually from bad settings, leakage or transients.

A nuisance trip is an unwanted operation of a breaker, RCD or relay when nothing needed clearing. Usual causes are cumulative earth leakage from many electronic loads on one RCD, inrush on transformer or LED circuits, harmonics heating thermal elements, poorly coordinated settings and CT wiring errors. Repeated nuisance trips tempt people to raise settings or bypass protection, which is how genuine faults later go unnoticed.

Heard on the job

That 30 mA RCD on the server room circuits keeps nuisance tripping, forty power supplies are leaking 22 mA before anything goes wrong.

Also heard as

  • false trip
  • spurious trip
  • unwanted trip