Equivalent direct radiation. One square foot of EDR gives off 240 Btu per hour on steam and about 150 Btu per hour on hot water at standard conditions. Techs count the radiators, look up the EDR of each by height, columns and sections, total it, and then choose a steam boiler whose net rating matches the connected radiation. Sizing a steam boiler to heat loss instead leaves part of the system cold.
Counted 620 square feet of EDR in the building, so we need a boiler with at least 620 net, never mind the heat loss calc.
On steam, size to the radiation, not the house. It is the opposite of what most hot water techs are taught.