Point of no pressure change

phraseStandard termBoilers

The place in a closed hydronic loop, where the expansion tank connects, whose pressure the pump cannot change.

Because the tank's air cushion fixes the pressure at its connection, the circulator's pressure rise is added downstream of that point and its pressure drop subtracted upstream. Put the pump just after the tank and the whole system gains pressure when it runs; put it before the tank and parts of the system drop toward vacuum, pulling in air and causing pump cavitation and noise.

Heard on the job

Tank's on the return and the pump's on the return pumping into it, the point of no pressure change is in the wrong place, that's your air problem.

Also heard as

  • PONPC