Turndown

nounStandard termBoilers

The ratio of a burner's highest to lowest firing rate, such as 4 to 1 or 10 to 1.

A burner with 10 to 1 turndown can fire from full input down to one tenth of it while staying stable and clean. Higher turndown lets a boiler match light loads without shutting off, cutting short cycling and purge losses. On-off burners have no turndown, high-low burners have two steps, and modulating gas burners and mod-cons commonly reach 5 to 1 up to 10 to 1.

Heard on the job

Building load in April is 8 percent of design, with 4 to 1 turndown the boiler can't get that low and short cycles all day.

Insider tip

Turndown figures from a brochure are at ideal conditions; real stable turndown is often lower once the burner is tuned for low CO.

Also heard as

  • turndown ratio