Air-free CO

nounStandard termBoilers

Carbon monoxide in flue gas corrected to zero excess oxygen, so dilution with air cannot hide a CO problem.

Raw CO readings drop as more air dilutes the flue gas, which can make a bad burner look clean. Air-free CO scales the reading as if no excess air were present, using the measured O2. Appliance standards and many manufacturers treat 400 ppm air-free as the upper limit, and a well-tuned gas boiler usually reads well under 100 ppm.

Heard on the job

Air-free CO is 620 at high fire, that burner's not going back in service until I find where the air's short.

Also heard as

  • CO air-free
  • COAF
  • CO corrected to 0 percent O2