Smoke spot

nounStandard termBoilers

An oil burner test that pulls flue gas through filter paper and grades the dark spot from 0 to 9.

A hand pump draws a fixed volume of flue gas, usually ten strokes, through a strip of filter paper, and the spot is compared with a printed scale where 0 is clean and 9 is black. Oil burners are set for zero or a trace of smoke before final adjustments are made for O2 and CO2. A high smoke number means soot will build up on the heat exchanger and stack temperature will climb.

Heard on the job

Smoke spot's a 3, open the air band a touch and pull another one before you go chasing the CO2.

Also heard as

  • smoke spot test
  • smoke test
  • Bacharach test