Superheat

nounStandard termHVAC

How many degrees refrigerant vapor is above its boiling point at the pressure it is at.

Measured at the evaporator outlet or the outdoor unit's suction line, superheat equals actual suction line temperature minus saturation temperature read from suction pressure. It proves that all the liquid has boiled off before the compressor. Fixed orifice systems are charged to a target superheat from a chart using indoor wet bulb and outdoor dry bulb; low superheat risks floodback, high superheat means a starved coil.

Heard on the job

Suction saturation's 42 and the line's 64, that's 22 superheat, it's low on charge or the TXV's starving it.

Insider tip

Clamp the probe on clean, bare suction line near the service valve and let the system run 15 minutes before trusting the number.

Also heard as

  • SH
  • suction superheat

Do not mix it up with

  • Subcooling: Superheat is measured on vapor in the suction line; subcooling is measured on liquid in the liquid line.