Starved

adjectiveShop talkHVAC

Describes an evaporator not getting enough refrigerant, so part of the coil runs warm and superheat is high.

A starved coil shows high superheat, low suction pressure and only the first few passes cold to the touch. Causes include low charge, a restricted drier or metering device, a TXV with a lost bulb charge or plugged screen, or flash gas in the liquid line. Capacity drops, and the compressor runs hot because the suction gas that cools it is too warm and too thin.

Heard on the job

Coil's starved, only the bottom third is sweating and superheat is 30, check subcooling to see if it's charge or restriction.

Also heard as

  • starving
  • underfed

Do not mix it up with

  • Floodback: A starved coil gets too little refrigerant and shows high superheat; floodback is too much refrigerant and near-zero superheat.