Hunting

nounShop talkHVAC

A TXV or control swinging back and forth, alternately overfeeding and starving the evaporator instead of settling.

A hunting expansion valve opens wide, floods the coil and drops superheat to near zero, then clamps down and lets superheat soar, over and over. Causes include an oversized valve, a bulb mounted in the wrong spot or loose, flash gas in the liquid line, and very light loads. Watching superheat on a data logger for several minutes is the way to catch it.

Heard on the job

Superheat's bouncing between 2 and 20 every minute, the TXV's hunting, check where that bulb is clamped.

Also heard as

  • TXV hunting
  • valve hunting