IPLV

abbreviationStandard termHVAC

Integrated part load value: a single weighted chiller efficiency figure that reflects operation at 100, 75, 50 and 25 percent load.

Integrated part load value. Chillers spend most of their hours well below full load, so IPLV weights efficiency at the four load points at 1, 42, 45 and 12 percent respectively, under standard condenser water relief. It is usually stated in kilowatts per ton for large chillers, where lower is better. NPLV applies the same weighting at a project's own design conditions.

Heard on the job

Full-load kW per ton is about the same on both chillers, but the variable-speed one's IPLV is 0.38 against 0.55.

Also heard as

  • integrated part load value