DCV

abbreviationStandard termHVAC

Demand-controlled ventilation: adjusting outdoor air in real time to match how many people are actually in a space.

Demand-controlled ventilation. CO2 sensors, occupancy sensors or people counters tell the controls how full a space is, and the outdoor air damper or ventilation fan modulates between a base rate for the building and the full rate for design occupancy. It saves the most in spaces with big swings in occupancy, such as gyms, auditoriums and meeting rooms, and codes require it in many of them.

Heard on the job

DCV has the auditorium at minimum outside air with 400 people in there, the CO2 sensor is reading outdoor air, it's mislocated.

Also heard as

  • demand-controlled ventilation
  • demand control ventilation